ABE top
ABE Homepage ABE Centennial
Agricultural and Biosystems Engineering
ABE Home

About ABE

Prospective Students


Undergraduate Students

Graduate Students


Industrial Technology
  Program


Faculty and Staff

Extension and Outreach

Research

Events and News

MWPS

Locator Map

Search


Choosing Fans for Livestock and Poultry Ventilation
 
------------------------------------------------
ISU Publication #: Pm1587
Authors: Jay D. Harmon and Hongwei Xin
Department of Agricultural and Biosystems Engineering
Iowa State University
Date: 2/95
 
Introduction
 
     Fans are an important component of any mechanically ventilated livestock or poultry house. They are the driving force behind the exchange of air that is necessary to create a healthy environment for animals and associated farm workers. Other components of the ventilation system, such as the inlets and control circuitry, are used to harness the quantity of air exchanged to create an acceptable and uniform building environment.
 
Quantifying Quality
 
To understand the principles of fan selection, basic terms must be understood.  These include:
 
Air Delivery:  Air delivery is the amount of air that a fan will move in a given situation.  This term is expressed as volume of air movement per unit time.  The standard unit is cubic feet per minute (cfm). 
 
Static Pressure: Static pressure is the difference in pressure that a ventilation fan creates between the inside and outside a mechanically ventilated structure. Static pressure may be measured using a manometer, (Figure 1).  Fans are used to create a vacuum within a building by exhausting air.  The indoor environment, having a lower pressure than the outside environment, will draw air in through inlets (Figure 2). This is called a negative pressure system. In most animal housing situations, the static pressure of the ventilation systems is between 0.04 and 0.06 inches of water. A free hanging fan, such as a stirring fan, will create no static pressure.
 
Efficiency:  The efficiency of a fan is generally rated as air delivery rate per unit of energy. Most ratings use the units of cfm per watt (cfm/W).
 
Important Criteria
 
When choosing a fan there are several important criteria that should be considered.  These include:
 
     Quantity of air delivered at different static pressures,
 
     Energy Efficiency,
 
     Quality of dealer service and support,
 
     Reliability and life,
 
     Suitability for intended application,
 
     Cost.
 
 
     These criteria must be considered and weighed against each other. Fans should not be chosen solely using the criteria of first cost.
 
Fan Rating
 
     Never assume that two fans of equal size will perform the same.  Fans from different manufacturers may perform much differently. For instance, it has been found through testing of several 24 inch fans that the air delivery ranged from 3410 to 6960 cfm, and the efficiency ranged from 8.2 to 15.3 cfm/W.
 
     Fans should be rated to show performance as a function of static pressure. This information will be presented by using either a graph or table. When purchasing fans, a performance table should be provided.  An example of this information appears in Table 1. This information should be based on tests performed using the fans as it will normally operate, including use of guards, shutters, discharge cones and other accessories. Beware of using manufacturers' data if it is not backed by an independent laboratory.  Two laboratories, the Air Movement and Control Association (AMCA) in Chicago and the Bioenvironmental and Structural Systems (BESS) lab at the University of Illinois, are known to test fans impartially.  AMCA has been the industry standard for many years. Fans that have been tested by AMCA will carry a decal similar to the one in Figure 3.
 
     Efficiencies generally are better for larger fans than small ones.  For instance, a good rating for a 24-inch fan at 0.1 inches of water is 12 cfm/W, while a 36-inch fan should have an efficiency of 17 cfm/W and a 48-inch fan should have one equivalent to 19.
 
Table 1. Example fan data for a 24-inch fan with shutter, guard and discharge cone.
 
 
Static
Pressure   Speed      Airflow      Efficiency
in. water    rpm         cfm            cfm/W
0.00         1078        6590            16.6
0.04         1073        6268            15.5
0.05         1071        6178            15.1
0.10         1065        5750            13.7
0.15         1061        5333            12.5
0.20         1058        4798            11.1
0.25         1060        4137            9.7
0.30         1074        2020            5.1
 
     Typically, mechanical ventilation systems include multiple fans.  Various ventilation rates are needed due to the ever-changing outdoor temperature. A minimum ventilation rate is established to maintain a degree of air quality in the building during the winter.  A maximum ventilation rate is established during the summer at a point where additional ventilation will not cool the building further. To bridge between these points, several fans may be used to achieve the various required ventilation rates.  This is called "fan staging".  For example, consider a building that requires 1000 cfm in the winter and 13,000 cfm in the summer.  A minimum ventilation fan would be selected that provides approximately 1000 cfm.  The next fan stage might provide 7000 cfm; 1000 from the minimum ventilation fan and 6000 cfm from a second fan.  The third stage might add another 6000 cfm for a total of 13,000 cfm. By staging fans, a relatively constant environment may be maintained. When selecting fans for animal housing, use the rating at 0.125 inches of water to add a safety factor.  Pit fans and fans used with evaporative pads use different static pressure criteria.
 
Factors Affecting Fan Performance
 
     The configuration in which a fan is installed and the manner in which it is maintained greatly affects the performance.  Guards generally decrease the fan performance less than 5 percent.  Guards should always be left in place since they protect the fan from objects, and protect workers from the fan.
 
     Shutters reduce fan performance from 10 to 25 percent.  If fans are to run continuously, shutters should not be installed since they serve no useful purpose in this situation.  Dirty shutters can reduce air delivery by as much as 40 percent.  Regular cleaning and maintenance keeps shutters operating at their manufactured level of efficiency. Use graphite products for lubrication to prevent dust from sticking to lubricated parts.
 
     If belt driven fans are used, belt tension should be checked regularly. Belts that are loose will cause the fan to be less efficient and contribute to belt wear. An over-tight belt will cause undue wear on bearings.  Discharge cones and other well designed fan housing can increase fan efficiency by 15 percent or more. This is due to reduced air turbulence of air entering or leaving the fan.
 
Fans for Specialized Uses
 
     In certain situations, specific fan characteristics are needed for specialized situations.  Mixing fans are generally selected for the ability to throw air.  This is accomplished by use of special shrouds and deflectors that create a jet of air which travels further than normal fan discharge.  Mixing fans are considered to operate at "free air" or zero inches of static pressure.  Ceiling fans are also used for mixing and are not easily rated because they are free air fans.  Most ceiling fans have small motors and are relatively efficient. They do a good job in situation where temperature stratification is a problem, or if air movement is needed in pens with solid partitions.
 
     Minimum ventilation fans are used to provide ventilation air during cold conditions.  Generally, these fans are sized by calculating a required quantity of air to insure proper air quality. The fan selected then provides this amount of ventilation air either by running continuously, by running on a
variable speed or by intermittent operation using a cycle timer. These fans
should have the characteristic of being influenced little by changes in static pressure.  In other words, air delivery at 0.04 and 0.1 inches of static pressure should be nearly equal.  This is to prevent substandard ventilation during windy winter conditions.  Use the rated air delivery at 0.125 inches of static pressure to select minimum ventilation fans.  If minimum ventilation fans run continuously do not install shutters.
 
     Fans used for under-slat ventilation or pit fans should have sealed motors and made of corrosion resistant materials. If they are used on a pit duct, a fan that will move the required air at 0.25 to 0.30 inches of water should be selected.  Deep pit buildings should use pit fans for minimum ventilation.
 
     Fans used in livestock ventilation systems using evaporative cooling pads should be sized to provide the necessary air flow at higher static pressure.  This is necessary because of increased resistance from drawing air through wetted pads. Fans used to draw air through evaporative pads should be sized based on static pressure of 0.15 to 0.2 inches of water, depending on the thickness and material of the evaporative pad.
 
 
Fan Installation
 
     The location and wiring of fans are essential to good performance and safety of operation. The following are some guidelines to fan installation:
 
1. Fans should be installed on a side opposite the prevailing winds if possible. If a sheltered area is not available, commercially available fan shrouds help to reduce the effect of wind on fan performance.
 
2. Inlets should not be installed within 8 feet of fans.  When installed closer, short circuiting of the ventilation system by exhausting fresh air rather than mixing it within the building may occur.
 
3. Motors must be securely fastened to a rigid, flat surface to prevent vibration and minimize noise.
 
4. Fan motor circuits should have:  branch circuit overcurrent protection to protect circuit conductors against short circuits and ground fault currents,
 
     a power disconnect to completely disconnect the motor from the power
     supply,
 
     a controller to start and stop the motor and to interrupt the current if the
     motor fails,
 
     an overload protection device to disconnect an overloaded motor.
 
  
5. Increase wire size when locating motors a distance from the power source.  Wire size must be adequate to minimize voltage drop during starting and running.  Inadequately sized wire can cause motor failure. Table 2 gives proper copper wire conductor sizes.
 
Size of Openings
 
     Although fans are a necessary part of a mechanical ventilation system, they are not the only thing to consider. Also needed is some way to bring air into a negative pressure system. A standard rule for sizing air openings is to provide one square foot of area for every 800 cfm of capacity. Inlet placement is the key to good distribution of fresh air.
 
Summary
 
     Good quality fans are essential for proper performance of mechanically ventilated livestock facilities.  Fans that are inefficient can add to production cost in two ways.  The most obvious cost is wasted energy that is expended while using an inefficient fan. Another cost, and one that probably has a much greater effect on profit, is that associated with poor air quality with the building. Fans that are inefficient do not move as much air as one might think.  This allows air quality to diminish and therefore stresses animals.  Stress to animals can lead to disease problems as well as less than optimal animal growth and feed conversion.
 
     As a rule of thumb, the best way to choose a proper fan is to shop around and compare based on independent lab ratings.  The extra time will save you money in the long run.
 
     For more information on proper ventilation rates see your local county
Extension agent.
Table 2. Copper Wire Conductor Sizes for Single Phase Motors.
 
 Distance of Wire Run (feet)
 
       50 ft    100 ft      150 ft    200 ft    250 ft
HP   115V 230V 115V 230V  115V 230V 115V 230V  115V 230V
1/8  12   12    12  12   10   12    10  12   10   12
1/6  12   12    12  12   10   12    8  12     8   12
1/4  12   12    10  12     8   12    6  12     6   12
1/3  12   12    10  12     8   12    6  12     6   12
1/2  10   12    8  12     6   12    4  12     4   10
3/4  10   12    6  12     4   10    4  10     3   8
1    10   12    6  12     4   10    4  10     3   8
1.5    8   12    6  10     4   10    3    8     2   6
2      8   12    4  10     4   10    2    8     1   6
3      6   12    4    8     2   6    1    6     0   4
 

Back to Livestock

ABE bottom

Copyright© 2002. College of Engineering. Iowa State University. All rights reserved.